In the light of COVID-19 outbreak, for the safety of community, Online orders are temporarily shut until further notice
ZEB-OU6KETX16
ZEB-OU6KETX16
ZEB-OU6KETX16
  • Availability: in stock In stock Out of stock You can purchase this product but it's out of stock

ZEB-OU6KETX16

Rs. 70,600.00
ZEBRONICS Online UPS embedded with isolation transformer, will eliminate common mode noise and the need to install expensive dedicated circuits, it provides reliable galvanically isolated power to critical equipment. Fully coated PCBAs to withstand harsh environments.
  • Barcode:
DESCRIPTION
FEATURES
Galvanic isolation design to withstand all kinds of load
Fully coating PCBAs to withstand harsh environment
Unique ventilation design for effective heat dissipation
Wide input voltage and frequency range to withstand robust environment
High short-circuit and overload capabilities
Built-in Maintenance bypass switch
SPECIFICATION
MODEL ZEB-OU10KETX16
PHASE Single phase with ground
CAPACITY 6KVA/4.8KW
INPUT
Nominal Voltage 208VAC/220VAC/230VAC
Voltage Range 165VAC ~ 285VAC @ 16 pcs of batteries ; 185VAC ~ 285VAC @ 18 pcs of batteries
Frequency 40 Hz ~ 55 Hz @ 50Hz system ; 56 Hz ~ 64 Hz @ 60Hz system
OUTPUT
Output Voltage 208VAC/220VAC/230VAC
Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦ 3 % THD (Linear Load) ; ≦ 5 % THD (Non-linear Load)
Transfer Time
\
AC to DC : Zero
\ Inverter to Bypass : Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode 88.30%
Battery Mode 92%
BATTERY
Long-run Model
Battery Type Depending on the applications
Battery Numbers** 16 pcs, 18 pcs
Charging Current (max.) Default 8A, 2A/4A/8A (adjustable)
Charging Voltage 218.4 V ± 1%, 245.7 V ± 1%
INDICATORS
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continously sounding
PHYSICAL
Long-run Model
Dimensions, D x W x H (mm) 562 x 250 x 830
Net Weight (Kgs) 62
ENVIRONMENT
Operating Temperature 447
Operating Humidity < 95 % and non-condensing
Noise Level Less than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Dry Contact Five signals: AC failure, low battery, UPS alarm, bypass and UPS fault
Optional SNMP Power management from SNMP manager and web browser
\
\ \

 

RECENTLY VIEWED PRODUCTS