Zeb-OU15KE3P1P

Sale priceRs. 182,600.00

ZEBRONICS Online UPS comes with True double-conversion. Provides better Output power factor of 1 with higher performance and efficiency for critical applications. Supports programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devices. It's also suitable for laser printers and ultrasound load
Product Type: Online UPS

Features

True double-conversion
DSP technology guarantees high reliability
Output power factor 1.0
Active power factor correction in all phases
50hz/60hz frequency converter mode
ECO mode operation for energy saving
Emergency power off function (EPO)
Optional parallel operation
Smart battery charger design to optimize battery performance
Maintenance bypass available
Adjustable battery design
Country of Origin :  China

Specifications

MODEL ZEB-OU15KE3P1P
PHASE 3-phase in / 1-phase out
CAPACITY 15KVA / 15KW
PARALLEL CAPABILITY up to 6 units in parallel
INPUT
Nominal Voltage 3 x 380/400/415 VAC (3Ph+N)
Voltage Range -30% ~ +20%
Frequency Range 40~70 Hz
Power Factor ≧ 0.99 @ 100% Load
Harmonic Distortion (THDi) < 3% at full linear load
OUTPUT
Output Voltage 1 x 220*/230/240 VAC (1Ph+N)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50/60 Hz ± 1%
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦ 1 % THD (Linear Load) ; ≦ 3 % THD (Non-linear Load)
Transfer Time
\
AC Mode to Batt. Mode : Zero
\ Inverter to Bypass : Zero
Waveform (Batt. Mode) Pure Sine wave
Overload Capability 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% or 400ms
BYPASS
Nominal Voltage 1 x 220*/230/240 VAC (1Ph+N)
Voltage Range -30% ~ +20% (Adjustable)
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Overload Capability


"> 130% 1 minute (default)
Continously working until breaker protection (optional)"
EFFICIENCY
AC Mode 0.96 %
ECO Mode 0.99 %
Battery Mode 0.96 %
BATTERY
Long-run Model
Battery Type Depending on the applications
Numbers +/-16 pcs ~ +/- 20 pcs (Adjustable)
Charging Current (max.) 1A ~ 12A (Adjustable)
Charging Voltage +/-13.65V x N (N=16~20)
PHYSICAL
Long-run Model
Dimension,DxWxH (mm) 630 x 250 x 826
Net Weight (kgs) 43
ENVIRONMENT
Operation Temperture 0-40°C
Operation Humidity < 95% and non-condersing
Altitude** 0 ~ 1500m at full load
Noise Level Less than 60dB @1 Meter
MANAGEMENT
Smart RS-232 / USB Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
*If output voltage is set as 1 x 240VAC, the output power of the unit will be de-rated to 90%.
"**If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.
\ Product specifications are subject to change without further notice."
*** Transformer weight not included