No Products in the Cart
Line-interactive UPS | |
Double Boost | |
Automatic Voltage Regulation(AVR) | |
Wide Input Range(140V-300V) | |
With MCU control | |
Generator Compatible |
Capacity | 600VA/360W | |
Input | ||
Voltage | 220-240VAC | |
Voltage Range | 140-300VAC | |
Frequency | 50/60Hz (Auto Sensing) | |
Input Type | Input Plug | |
Input Protection | Fuse in PCBA | |
Output | ||
Voltage | 220-240VAC | |
Boost1 Ratio | 1.2 | |
Boost2 Ratio | 1.4 | |
Buck Ratio | 0.85 | |
Output Voltage Range(batt.mode) | +/-10% | |
Frequency Range(batt.mode) | 50/60Hz +/- 1% | |
Transfer Time | 4ms Typical | |
Waveform (batt.mode) | Simulated Sine-wave | |
Outlet Type | 3 AC Sockets | |
Full Protection | Overload, Short Circuit, Over discharge and Over charge | |
Line Mode Overload | >(110%±10%) fault after alarm 1min\ >(120%±10%) fault immediately | |
Battery Mode Overload | >(110%±10%) fault after alarm 1min \ >(120%±10%) fault immediately | |
Battery | ||
Battery Type | 12V7Ah (1 unit) | |
Charger Current | 1.5A(normal mode) | |
Recharge Time | 6 hours to 90% after complete discharge | |
Indicator | ||
Display | 1 LED | |
Alarm | ||
Battery Mode | Sounding every 30 seconds | |
Low Battery | Sounding every 2 seconds | |
Overload | Sounding every 0.5 seconds | |
Fault | Continuous sounding | |
Physical | ||
Dimension (mm), W x H x D) | 96 x 138 x 286 | |
Weight | ||
Net Weight | 4.14kg | |
Operating Environment | 0- 40°C, 0-90 % relative humidity (non-condensing) | |
Noise Level | Less than 40dB |