True double-converssion
  DSP technology guarantees high reliability
  Output power factor 1.0
  Active power factor correction in all phases
  ECO mode operation for energy saving
  Emergency power off function (EPO)
  Optional parallel operation
  Smart battery charger design to optimize battery performance
  Maintenance bypass avaliable
  Adjustable battery design
  MODEL ZEB-OU15KETX3P1P***
  PHASE 3-phase in / 1-phase out
  CAPACITY 15KVA / 15KW
  PARALLEL CAPABILITY up to 6 units in parallel
  INPUT  
  Nominal Voltage 3 x 380/400/415 VAC (3Ph+N)    
  Voltage Range -30% ~ +20%    
  Frequency Range 40~70 Hz    
  Power Factor ≧ 0.99 @ 100% Load    
  Harmonic Distortion (THDi) < 3% at full linear load
  OUTPUT  
  Output Voltage 1 x 220*/230/240 VAC (1Ph+N)    
  AC Voltage Regulation (Batt. Mode) ± 1%  
  Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz    
  Frequency Range (Batt. Mode) 50/60 Hz ± 1%    
  Current Crest Ratio 3:1 (max.)    
  Harmonic Distortion ≦ 1 % THD (Linear Load) ; ≦ 3 % THD (Non-linear Load)    
  Transfer Time
 
AC Mode to Batt. Mode : Zero
Inverter to Bypass : Zero
  Waveform (Batt. Mode) Pure Sine wave
  Overload Capability 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% or 400ms
  BYPASS  
  Nominal Voltage 1 x 220*/230/240 VAC (1Ph+N)
  Voltage Range -30% ~ +20% (Adjustable)
  Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
  Overload Capability
 
"> 130% 1 minute (default)
 Continously working until breaker protection (optional)"
  EFFICIENCY  
  AC Mode 0.96 %
  ECO Mode  0.99 %
  Battery Mode  0.96 %
  BATTERY  
  Long-run Model    
    Battery Type Depending on the applications  
    Numbers +/-16 pcs ~ +/- 20 pcs (Adjustable)
    Charging Current (max.) 1A ~ 12A (Adjustable)    
    Charging Voltage +/-13.65V x N (N=16~20)   
  PHYSICAL  
  Long-run Model    
    Dimension,DxWxH (mm)   630 x 250 x 826    
    Net Weight (kgs)   43   
  ENVIRONMENT  
  Operation Temperture 0-40°C
  Operation Humidity < 95% and non-condersing
  Altitude** 0 ~ 1500m at full load
  Noise Level Less than 60dB @1 Meter
  MANAGEMENT  
  Smart RS-232 / USB Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC
  Optional SNMP Power management from SNMP manager and web browser
     
  *If output voltage is set as 1 x 240VAC, the output power of the unit will be de-rated to 90%.
  "**If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.
 Product specifications are subject to change without further notice."
  *** Transformer weight not included